XM3.1-915-HP
Power Supply
 
 

Alarms
 

Battery
 

Power Supply
Model ALPHA/XM3.1-915-HP
Firmware V1.02.0
Major Alarm OK
Minor Alarm OK
Operational Mode Line
Charger Mode Float
Tamper Closed
Power Supply Language English
Power Supply Priority Normal
Input
AC Line Mode OK
Voltage 124.12 V
Current 3.88 A
Power 448 W
Frequency 60 Hz
Tap Status Buck tap
Frequency Range 3.00 Hz
Current Limit 17.00 A
Input Power Consumption 11,135 Wh
Output
Voltage 86.52 V
Power 330 W
Apparent Power 393.66 VA
Frequency 60.02 Hz
Percent Load 30.20 %
Output Setting 90 V
Output Regulation Fine
Over-current Tolerance 3.000 sec
Retry Delay 60 sec
Retry Limit 20
Active Drop Alarm OK
Active Drop Threshold 50 W
Current 4.55 A
Inverter
Inverter Status Off
End of Discharge Type String
End of Discharge Level 1.75 V/cell
Reduced Peak Mode Disable
Total Standby Events 45
Time Since Last Standby Event 81d 10h:15m
Time in Last Standby Event 0d 0h:01m
Total Time in Standby 519 min
Standby Events Since Reset 3
Time in Standby Since Reset 2 min
Time Since Reset 368 day(s)
Total Run Time 368 day(s)
Transformer Run Time 368 day(s)
Total Downtime 0d 0h:00m
Oil Cap Lifespan Consumed 15.8 %
Self Test
Deep Discharge Cycle Timed
Test Countdown 3 day(s)
Test Duration 10 min
Test Interval 30 day(s)
Test Inhibit No

 